Type K passes the speed test for power plant damper operation

25/10/2012


Type K passes the speed test for power plant damper operation

The swift performance capability of the Rotork Type K vane type damper drive has provided the successful retrofit solution to a critical application involving the safe and efficient operation of balanced-draft power generation boilers.

Inlet draft (ID) fan inlet dampers at power stations regulate the fan-induced pressure and airflow supply to balanced-draft power generation boilers. These boilers require a consistent internal operating pressure for efficient and safe combustion. Boiler pressure fluctuations create combustion problems that can, in extreme conditions, lead to catastrophic failure and structural damage. The maintenance of consistent operating pressure relies entirely on the swift operation of the ID fan inlet dampers.

At the three-unit 2735MW Florida Power & Light Manatee Power Station at Parrish, Florida, the ID fan inlet dampers demand full 90 degree damper movement at full torque load in three seconds or less in order to safeguard the operation of the boilers.

In a recent outage at the station it was necessary to replace the ID fan inlet damper drives on Units 1 and 2, which were over thirty years old and incompatible with the HART protocol of the station’s new Distributed Control System. In addition the manual overrides on the drives had proved to be unreliable.

The equipment selected to replace the obsolete equipment was Type K ‘PM Series’ pedestal mounted TK-6 damper drives, delivering a torque of 5000 lbs-ft at a tested time of less than three seconds for a full 90 degree stroke. Operated by vane-type direct drive pneumatic actuators, these units offer a smoother and faster acting performance than any alternative design.

Type K provided a ‘drop-in-place’ retrofit installation, matching the dimensions of the existing damper drive footprint on all eight of the replacement installations in Units 1 and 2. Integrated air volume boosters were fitted to obtain the required rotation speed and the control interface was provided by smart positioners.

Prior to delivery, Type K completed factory acceptance testing on the drives and obtained the test cycle times as recorded by the smart positioners. Test results were video recorded and documented for Florida Power & Light to review.

Installation was followed by witnessed acceptance testing during which the drives performed as quickly and smoothly at full load as the factory testing had indicated, contributing to a punctual return to boiler readiness for electricity generation.

Following the retrofit at Manatee Station Units 1 and 2, Type K has supplied four identical damper drives to the Florida Power & Light Martin Station on the east coast of Florida. The four remaining drives on Unit 3 at Manatee are programmed for replacement in 2013.